Redul B600 PLC

Redul B600 is a fault-tolerant real-time programmable logic controller, designed for the use in process industries, where additional electromagnetic protection, vandal-proof housing, and/or extended temperature range are preferred.


SKU: B600 XX XXX Category:
Overview

Applications

  • High-availability process control systems for
    • Steam and gas turbines (control and emergency protection)
    • Oil pumping stations and gas compressors
    • Main and auxiliary systems at power stations
    • Fire and gas systems
    • Water management systems
  • Fiscal applications (for example, LACT units)
  • Applications with unstable connection to upper level

General features

  • Real-time programmable logic controller
  • Modular configuration, allowing flexible extension and change of configuration
  • Supports up to 130,000 channels
  • Improved electromagnetic protection of the controller and enclosure of the modules, protective module form factor
  • In-module event archiving

Processing power and redundancy

  • Minimum application cycle time – 1 ms (5 ms with redundancy)
  • Scan time – 1 ms
  • Switchover in 5 ms
  • Processing of complex algorithms with powerful CPU modules and built-in microprocessors in I/O modules

System configuration

  • Up to 12 modules in a rack, up to 255 racks, up to 10 km (via fiberoptic line) between racks
  • RJ-45, SFP, or mixed connection between racks
  • Star, ring, or mixed network topologies
  • CPU module can be placed into any rack

Programming and visualization

  • Programming in Sigma LD software with IEC 61131-3 languages + CFC
  • Online application update
  • Remote configuration/maintenance and application updates
  • Special firmware with MySQL database server
  • Web visualization option in CPU modules
Specifications
Minimum application cycle time1 ms (5 ms in redundant configuration)
Scan time1 ms
Switchover time from main to standby controller5 ms
Timing accuracy 50 µs
ProcessorIntel Atom
RAM2 Gb
SSD4 Gb (optional up to 64 Gb)
Mean time between failures (MTBF) for a controller module>150,000 hours
Input power 85…264 VAC 18…36 VDC
120…370 VDC
I/O module size (W x H x D)30 х 267 х 186 mm
Operating temperature range -40…+60°С
ApprovalsCE, EAC, FCC-ready
Communications

Supported interfaces

  • RS-232 (9-pin, full duplex, speed 300–115, 200 bps, opto-isolation 500/1500 V, overvoltage protection)
  • RS-422/RS-485 (9-pin, speed 300–115, 200 bps, full-channel opto-isolation 500/1500 V, overvoltage protection) – up to 96 ports per controller
  • Ethernet 10/100/1000 RJ-45 (full duplex) – up to 4 ports per CPU
  • Ethernet 10/100/1000 fiberoptic (single-mode, multi-mode) – up to 2 ports per CPU

Built-in communication protocols*

  • IEC 61870-5-101 (master/slave)
  • IEC 61870-5-104 (master/slave)
  • Modbus RTU (master/slave, with expansion capabilities)
  • Modbus TCP (master/slave, with expansion capabilities)
  • OPC DA, OPC UA
  • EtherCAT

*Additional communication protocols, including non-standard ones, can be implemented according to your requirements.

Redundancy
  • Hot swapping of all modules
  • Hot-standby CPU modules
  • Dual ring high-speed internal data bus
  • Automatic power distribution among power supply modules
  • Redundancy of CPU, CPU sync, I/O modules, power supply modules, SCADA connection

100% Mirror/Duplicate Redundancy

Redul B600 —100% Mirror/Duplicate Redundancy

CPU and Power Supply Redundancy

Redul B600 — CPU and Power Supply Redundancy

Mixed Redundancy

Mixed Redundancy

Modules
Part numberDescriptionChannels (ports)
CPU MODULES
CU00052Central processor unit, CPU module
• Redundancy support
• Intel Atom
• 2 GB RAM, 1 × 4 GB SSD
• 1 × RS-232, 1 × RS-485
• 4 × Ethernet RJ-45
• GPS receiver

CU00052 (W) additionally includes web server with support of Web visualization
CU00062Central processor unit, CPU module
• Redundancy support
• Intel Atom
• 2 GB RAM, 1 × 4 GB SSD
• 1 × RS-232, 1 × RS-485
• 2 × Ethernet RJ-45, 2 × Ethernet SFP
• GPS receiver

CU00062 (W) additionally includes web server with support of Web visualization
CU00072Central processor unit, CPU module
• Redundancy support
• Intel Atom
• 2 GB RAM, 1 × 4 GB SSD
• 1 × RS-232, 1 × RS-485
• 2 × Ethernet RJ-45, 2 × Ethernet SFP
• 1 × DVI, 2 × USB host
• GPS receiver

CU00072 (W) additionally includes web server with support of Web visualization
POWER SUPPLY AND BUS EXTENSION MODULES
PP14011Power supply module 24 V DC, 75 W
• Redundancy support
• Bus extension ports (IN, OUT), RJ-45
PP14021Power supply module 24 V DC, 75 W
• Redundancy support
• Bus extension ports (IN, OUT), SFP
PP14031Power supply module 220 V AC/DC, 75
• Redundancy support
• Bus extension ports (IN, OUT), RJ-45
PP14041Power supply module 220 V AC/DC, 75 W
• Redundancy support
• Bus extension ports (IN, OUT), SFP
COMMUNICATION
MODULES
CP04011Communication processor RS-485 (Modbus RTU, IEC-61870-5-101, user protocols), 4 ports4
ANALOG MODULES
AI16011Analog input, AI module (current)
• Current measuring range: 0…20 mA, 4…20 mA
• 16 channels
• Resolution: 14 bits (including overflow)
• Measurement error under normal conditions: ±0.1%
• Common galvanic isolation
16
AI08021Analog input, AI module (current, HART)
• Current measuring range: 0…20 mA, 4…20 mA
• 8 channels
• Resolution: 16 bits (including overflow)
• Measurement error under normal conditions: ± 0.1%
• Built-in HART protocol
• 1 ADC and 1 HART-modem for each channel
• Channel galvanic isolation
8
AI08031Analog input, AI module (thermal resistances, thermocouples)
• Thermal resistance measurement range: 1…450 Ohm
• 8 channels
• Supported thermal resistances: Cu50, Cu100, Pt50, Pt100, Ni50, Ni100
• Supported thermocouples: R, S, B, J, T, E, K, N, A-1, A-2, A-3, L
• Resolution: 24 bits (including overflow)
• Measurement error under normal conditions: ±0.1%
• Common galvanic isolation

8
AI08041Analog input, AI module (current, voltage; high-accuracy)
• Current measuring range: 0…20 mA, 4…20 mA
• Voltage measuring range: 0…+10 V, -10…+10 V
• 8 channels
• Resolution: 16 bits (including overflow)
• Measurement error under normal conditions: ±0.025%
• Channel galvanic isolation
• Individual ADC for each channel
8
AO08011Analog output, AO module (current)
• Output range, current: 0…20 mA, 4…20 mA
• 8 channels
• Resolution: 16 bits
• The error of the formation of the control signal under normal conditions: ±0.1%
• Channel galvanic isolation
8
AO08021Analog output, AO module (current, HART)
• Output range, current: 0…20 mA, 4…20 mA
• 8 channels
• The error of the formation of the control signal under normal conditions: ±0.1%
• Built-in HART protocol
• Channel galvanic isolation
8
DIGITAL MODULES
DI32011Digital input, DI module
• Input current: 24 VDC
• 32 channels (4 groups by 8 channels)
• Group galvanic isolation
32
DO32011Digital output, DO module
• Output current: 24 VDC / 0.5 A
• 32 channels (4 groups by 8 channels)
• Group galvanic isolation
32
COUNTER MODULES
DA03011Counter/digital module
• Channel supply voltage: 3, 5, 12, 24 V
• Frequency measurement range: 1 Hz … 500 kHz
• Frequency generation range: 1 Hz … 10 kHz
• Pulse measurement range: 1…264 (with overflow)
• Frequency measurement error under normal conditions: less than ± 0.01%
• Pulse-counting error: ±1 pulse
• 3 × counter channels
• 1 × generator channel
• 6 × DI channels, 24 V
• 6 × DO channels, 24 V / 0.5 A
• Channel galvanic isolation of the counter channels
3/1/6/6
DA03022Counter/digital module
• Channel supply voltage: 5, 12, 24 V
• Frequency measurement range: 1 Hz … 500 kHz
• Frequency generation range: 1 Hz … 10 kHz
• Pulse measurement range: 1…264 (with overflow)
• Frequency measurement error under normal conditions: less than ± 0.01%
• Pulse-counting error: ±1 pulse
• 3 × counter channels
• 1 × generator channel
• 6 × DI channels, 24 V
• 6 × DO channels, 24 V / 0.5 A
• Built-in software for electronic overspeed trip
• Support of magnetic RPM sensor
• Channel galvanic isolation of the counter channels
3/1/6/6
CHASSIS
CH07011Chassis with 7 slots (1 PP and 5 expansion slots)
CH14011Chassis with 14 slots (1 PP and 12 expansion slots)
OTHER
OO00000Empty module (slot cover)
Downloads

Certificates
EC Declaration of Conformity

Manuals
To download complete manuals for Redul B600 controllers, please, send an e-mail to support@gp-systems.com

Dimensions

Overall and Installation Dimensions